DA-OC-5G Outdoor Cabinet
Dawnergy’s DA-OC-5G series are modular designed outdoor cabinets for wireless communication equipment. They are featured by flexible configuration, quick assembling and easy expansion.
Features
Applications
Cabinet Specifications
| Item | Specifications |
| Dimensions (W x D x H) (mm) | 650 x 650 x1500 (including base) |
| Voltage Input | AC 230V±10% |
| Color | Grey |
| IP Rating | IP55 |
| IP Code Standard | IEC60529 |
| Mounting Option | Floor-mount |
| Material | Galvanized steel (single layer) |
| Cooling Option | DC48V Fan with thermostat (When the temperature in the cabinet exceeds 40℃, the fan will operate automatically) |
| Thermostat | KSD301 |
| Door Switch | Deek Robot PS056-01N-200 |
| Rack Mount Hole Type | M6 square holes |
| Lighting | 48V 3W LED lamps |
| Lightning protection | Maximum flow capacity: 40kA, protection level: 1500V, response time: < 25nS |
| Environmental Requirements | |
| Ambient Temperature | -20℃ ~ 45℃ |
| Storage Temperature | -40℃~70℃ |
| Internal Relative Humidity of Cabinet | ≤85%(+30℃) |
| Storage Humidity | 0~100% |
| Atmospheric Pressure | 70~106KPa |
Outdoor Cabinet Standard Package
| No. | Name | Unit | Quantity |
| 1 | Key | piece | 2 |
| 2 | Square Nut | set | 10 |
| 3 | Screw | set | 10 |
| 4 | M12 Expansion Bolt | set | 4 |
| 5 | Sealing Putty | Kg | 1 |
Embedded Power System
embedded power system is composed of a motor frame, a monitoring module and a rectifier module; The power system has DC power distribution function, power monitoring to provide support for external signal input, communication transfer function and AC-DC detection, contactor control and other functions, the whole machine performance is stable, practicability is strong, can be background software operating system.![]()
Specifications
| Rectifier Module | Monitoring Module | Power Distribution | Note |
| GPR4830B1 | GPM48R |
AC power distribution: Single phase three wire input, total power bipolar AC circuit breaker (50A)
DC power distribution: Battery switch: 100A/1P *1 A power down: 63A/1P *3 Secondary power down: 16A/1P*2 |
Rectifier module (minimum 2, maximum 5) |
Dimension (mm)
![]()
GPR4830B1 Rectifier Module Specifications
| Item | Unit | Min. | Typical | Max. |
| AC input voltage | Vac | 90 | 220 | 290 |
| AC input voltage frequency | Hz | 45 | 50 | 65 |
| Input power factor | 0.99 | |||
| Output voltage range | Vdc | 42 | 54 | 58 |
| Output current | A | 0 | 30 | |
| Accuracy of output voltage stabilization | ±1% | |||
| Peak-peak Vp-p | mV | 200 | ||
| Output power | W | 0 | 1600 | |
| W | 0 | 800 | ||
| Output efficiency | % | 91 | ||
| % | 83 | |||
| Input overvoltage protection | Vac | 288 | 305 | |
| Input overvoltage protection recovery point | Vac | 285 | ||
| Input undervoltage protection | Vac | 80 | ||
| Input undervoltage protection recovery point | Vac | 90 | ||
| Output overvoltage protection point | V | 58.5 | 59 | 61.5 |
| Output current limiting protection | A | 32 | 33 | 34 |
Monitoring Module Function
| Function | Instructions |
| The upper computer remote monitoring function to the monitoring unit | The upper computer can inquire, set and control the system monitoring remotely at any time to realize the function of "three remote" |
| Monitoring module to rectifier module management | The monitoring module sends control adjustment command or parameter acquisition command to the module through RS485 communication |
| Battery management | Management of "battery low voltage, battery under power, battery floating charge management, temperature compensation" |
| Monitor the system output management function | Inspection and control systems |
| LED indicator function | Signal indicate |
| LCD display | Menu to set, modify |
Battery
![]()
Features
Specifications
| Normal Voltage (v) |
Rated Capacity (Ah) 20hrs/25℃ |
Approx. Weight (kg) | Dimension (mm) |
| 12 | 200 | 54 | 522 (L) x 240 (W) x 230 (H) |
Contact Us at Any Time